Illumination intensity norms as per SNiP 23-05-95
(Revision SP 52.13330.2011)

IMPORTANT! 
Illumination intensity norms are shown in the working surface luxes: if this is a cabinet, a reading room, or a billiard table, it is the height of the desk, usually 0.8 meters from the floor (G = 0.8); if it's a ladder, a lobby, a gym, a road, or a stadium, it's: floor, road canvas, field (G = 0.0).


Lighting of streets, roads and squares

Lighted objects Medium Illumination (Em), lx
at least
Light distribution (Emin/Em),
at least
Motorways, federal and transit routes. Road class - А 
1 А1. Motorways, federal and transit routes, main arteries of the city (outside the city centre) -with a capacity of more than 10 000 unit/h 30 0,35
2 А2. Other federal roads and main streets (outside the city centre)- with a capacity of 7 000-9 000 unit/h 20 0,35
3 А3. Central highways connecting streets with exit on the A1 (downtown)- with a capacity of 4 000-7 000 unit/h 20 0,35
4 А4. Main historical passes of the centre, internal links of the centre (in the centre of the city) -with capacity of 3 000-5 000 unit/h 20 0,35
Main roads and streets of the neighborhood. Road class - B
5 B1. Main roads and streets of the city of the district (outside the city centre)- with a capacity of 3 000-5 000 unit/h 20 0,35
6 B2. Main roads and streets of the city of the district (downtown)- with a capacity of 2 000-5 000 unit/h 15 0,35
Streets and roads of local importance. Road class - V
7 V1. Transport and pedestrian connections within residential areas and exit on the highway except for the streets with a continuous movement (living outside the city centre)- with a capacity of 1 500-3 000 unit/h 15 0,25
8 V2. Transport and pedestrian connections in residential neighbourhoods and motorways (living in the city centre) -with a capacity of 1 500-3 000 unit/h 10 0,25
9 V3. Transport links within production and public storage areas (in urban industrial, municipal and storage areas)- with a capacity of 500-2 000 unit/h 6 0,25
Isolated tram road
10 Isolated tram road 10 -
Streets and roads in rural settlements
11 Main streets, squares of social and trade centers 10 -
12 Main streets of residential buildings 6 -
13 Secondary (alleys) of the streets of a residential building 4 -
14 Village roads, orchards and suburbian cooperatives 2 -

Lighting of petrol stations (AZS) and parking lots





Lighted objects

Medium illumination
(Em),
lx
at least
Petrol stations
1 Access routes from A and B roads 15
2 Access roads from B roads 10
3 Oil refueling and discharge sites 20
4 The rest of the territory with a carriageway 10
Parking spaces, rolling stock holdings
5 Outdoor parking on the streets of all categories as well as outside streets, open parking spaces in the neighbourhoods between rows of boxing garages 6

Illumination of pedestrian spaces





Lighted objects

Medium illumination
(Em), lx
at least
Light distribution
(Emin/Em)
at least
1 P1. Sites in front of entrances to cultural, sporting, recreational and trading facilities, sports, recreational and trading facilities 20 0,30
2 P2. The main pedestrian streets of the historical part of the city and the main public centres of the administrative districts, impassable and factory areas, landing, children's and recreation areas 10 0,30
3 P3. Pedestrian streets, main and auxiliary entrances of parks, sanatoriums, exhibitions and stadiums 6 0,20
4 P4. Sidewalks separated from the roadways of roads and streets, major passages of neighbourhoods, entrances, passageways and central alleys of children's, educational and health facilities 4 0,20
5 P5. Secondary passages in the territories of neighbourhoods, management sites in the territories of neighbourhoods, side alleys and auxiliary entrances of city parks and central alleys of administrative districts 2 0,10
6 P6. Side alleys and auxiliary entrances of the administrative district parks 1 0,10

Illumination of underground and above-ground pedestrian crossings





Lighted objects

Medium illumination
(Em), lx
at least
Light distribution
(Emin/Em)
at least
1 Passages of underground pedestrian crossings and tunnels 75 0,30
2 Passages of above-ground pedestrian crossings with transparent walls and ceiling or glass wall openings 75 0,30
3 Stairways, exits and inspection sites of above-ground pedestrian crossings with transparent walls and ceiling or glazed wall openings 50 0,30
4 Ladders and ramps of underground pedestrian crossings and tunnels 45 0,30
5 Open footbridges 10 0,30

Lighting of entrances in buildings





Lighted objects

Medium illumination
(Em), lx
at least
1 Main entrance area 6
2 Backup and technical entrance area 4
3 On a pedestrian track long 4 m at the main entrance in building 4

Emergency lighting of escape routes





Lighted objects

Medium illumination
(Em), lx
at least
Light distribution
(Emin/Em)
at least
1 Routes for the evacuation of high-risk areas 15 0,10
2 Escape routes up to 2 m wide 1 0,025
3 Escape lighting of large squares 0,5 0,025

Duty and security lighting





Lighted objects

Medium illumination
(Em), lx
at least
1 Security lighting (without special equipment) 0,5

Lighting for administrative buildings (ministries, departments, committees, municipalities, offices, design and project organizations, research institutions, etc.)





Lighted objects

Medium illumination
(Em), lx
at least
1 Project rooms and rooms, design, drawing desks. (on tables, G 0.8). 500
2 Analytical Labs. (on tables, G 0.8). 500
3 Computer and reading halls. (on tables, G 0.8). 400
4 Labs: of organic and inorganic chemistry, thermal, physical, spectrographic, style metric, photometric, microscopic, x-ray analysis, mechanical and wireless measuring, electronics, preparatory. (on tables, G. 0.8). 400
5 Office and work rooms, offices. (on tables, G 0.8). 300
6 Visitors ' facilities, expeditions. (on tables, G 0.8). 300
7 Rooms for copying. (on tables, G 0.8). 300
8 Bound spaces. (on tables, G 0.8). 300
9 Design, carpentry and repair shops. (on tables, G 0.8). 300
10 Reading catalogs. (on the front of the files, V-1.0). 200
11 Conference rooms, meeting rooms. (on tables, G 0.8). 200
12 Recreations, lobbies, foyers. (on floor, G-0.0). 150
13 Depository and archives, public access facility. (On racks. V-1.0). 75

Lighting standards for banking and insurance institutions





Lighted objects

Medium illumination
(Em, lx
at least
1 Operating room, credit group, cash room. (on tables, G 0.8). 400
2 Server room, interbank electronic accounts rooms. (on tables, G 0.8). 400
3 Place of manufacture, processing of identification cards. (on tables, G 0.8). 400
4 Department of collection, collector. (on tables, G 0.8). 300
5 Facilities for the servicing of natural persons. (on tables, G 0.8). 300
6 Depository, supply closet, value store. (on tables, G 0.8). 200
7 Strong room (on tables, G 0.8). 150

Agency Lighting Standards of general education, primary, secondary and tertiary education





Lighted objects

Medium illumination
(Em), lx
at least
1 Classrooms, classrooms, study cabinets, general education laboratories, boarding schools, and specialized and vocational technical institutions. (on whiteboard). 500
2 Technical drafting and drawing rooms. (on tables, G 0.8). 500
3 Classrooms, classrooms, study cabinets, general education laboratories, boarding schools, and specialized and vocational technical institutions. (on tables, G 0.8). 400
4 Classrooms, study cabinets, technical laboratories and higher education institutions. (on tables, G 0.8). 400
5 Informatics and Computer Science rooms. (on tables, G 0.8). 400
6 Laboratories in classrooms. (on tables, G 0.8). 400
7 Service-type offices. (on tables, G 0.8). 400
8 Metal and wood processing workshops. (on tables, G 0.8). 300
9 Entertainers of the Act halls. (on the floor, G-0.0). 300
10 Offices and teachers ' rooms. (on tables, G 0.8). 300
11 Gyms. (on the floor, G-0.0). 200
12 Act halls, cinemas. (On the floor, G-0.0). 200
13 Recreations. (On the floor, G 0.0). 150
14 Covered pools. (On the surface of the water). 150
15 Gyms. (at a level of 2.0 m from the floor). 75

Lighting standards for recreational facilities





Lighted objects

Medium illumination
(Em), lx
at least

1

Multi-Purpose halls. (G-0.8).

400

2

Theater halls, concert halls. (G-0.8).

300

3

Mug rooms, musical classes. (G-0.8).

300

4

The auditoriums of clubs, the club is the living room, the room for leisure activities, meetings, and the foyer of the theatres. (G-0.8).

200

5

Exhibition halls. (G-0.8).

200

6

The lobby of cinemas, clubs. (On the floor, G-0.0).

150

7

The movies, the sound and the light rooms (G-0.8).

150

8

Cinema halls. (G-0.8).

75

Lighting Standards for nursery schools



Lighted objects

Medium illumination
(Em), lx
at least

1

Music and gymnastics, dining rooms. (On the floor, G 0.0).

400

2

Group, playing rooms. (On the floor, G-0.0).

400

3

Dressing rooms. (On the floor, G-0.0).

300

4

Medical office. (G-0.8).

300

5

Sick-bays, rooms for sick children. (On the floor, G-0.0).

200

6

Reception rooms. (on the floor, G 0.0).

200

7

Dormitories. (on the floor, G-0.0).

100

Standards for lighting sanatoriums, holiday homes, lodging houses



Lighted objects

Medium illumination
(Em), lx
at least

1

The classrooms of children's sanatoriums. (On the floor, G 0.0).

500

2

Rooms, dormitories. (On the floor, G 0.0).

100

Standards for the lighting of physical fitness facilities



Lighted objects

Medium illumination
(Em), lx
at least

1

Halls of sport games. (On the floor, G 0.0).

200

2

Aerobic halls, gymnastics, wrestling rooms. (On the floor, G 0.0).

200

3

Bowling. (on the floor, G-0.0).

200

4

Pool hall. (On the surface of the water).

150

5

The halls of sports. (at an altitude of 2 m, V-2.0).

75

Lighting standards for catering operations



Lighted objects

Medium illumination
(Em), lx
at least

1

Dining halls of restaurants, dining rooms. (G-0.8).

200

2

Handout rooms. (G-0.8).

200

3

Hot workshops, cold workshops, preparation and billet rooms. (G-0.8).

200

4

Washing rooms of kitchen and dining room, room for cutting bread. (G-0.8).

200

Store Lighting Standards



Lighted objects

Medium illumination
(Em), lx
at least

1

Shopping halls for self-service stores. (G-0.8).

400

2

Store Shopping Halls: bookstores, ready-made dresses, linens, footwear, tissues, fur products, headgear, perfumes, haberdashery, jewellery, electricity, and the food, without self-service. (G-0.8).

300

3

Fitting rooms. (V-1.5).

300

4

Main cash premises. (G-0.8).

300

5

Offices of order departments, service bureau. (G-0.8).

200

6

Store Shopping Halls: utensils, furniture, sporting goods, building materials, electrical appliances, toys and office supplies. (G-0.8).

200

Standards for the coverage of domestic services



Lighted objects

Medium illumination
(Em), lx
at least

1

Repair shops: watch repair, jewelry and engraver work. (G-0.8).

3000/300

2

Repair shops: construction and repair of the headgear, fur sewing work. (G-0.8).

2000/750

3

Repair shops: repair of shoes, galantere, metal, plastic products, household appliances. (G-0.8).

2000/300

4

Repair shops: rhoto-, film, radio and television repair. (G-0.8).

2000/200

5

Clothing and knitting Handicrafts rooms: sewing rooms, closed branches, clothing repair units. (on tables, G 0.8).

750

6

Laundry: clothing repair. (G 0.8).

750

7

Apparel Chemical Cleaning Shop: staining offices. (G-0.8).

500

8

Clothing and knitting Handicrafts rooms: departments of the hand and the machine strap. (G-0.8).

500

9

Photolabs. (G-0.8).

400

10

Hairdressing offices. (G-0.8).

400

11

Laundry: drying and ironing shops (manual). (G-0.8).

300

12

Clothing and knitting Handicrafts rooms: Application preparation offices. (G-0.8).

300

13

Clothing and knitting Handicrafts rooms: ironing steaming rooms (G-0.8).

300

14

Recording Studios: rooms for recording and listening, phonotechs. (G-0.8).

200

15

Rental points: Facilities for visitors. (G-0.8).

200

16

Apparel Chemical Cleaning Shop: Reception and clothing, dry-cleaning facilities. (G-0.8).

200

17

Laundries and self-service. (On the floor, G-0.0).

200

18

Laundry: Separation and Laundry divisions. (G-0.8).

200

19

Laundry: drying and ironing shops (mechanical). (G-0.8).

200

20

Laundry: Washing compartments, laundry, solution preparation, storage of washing materials. (G-0.8).

200

21

Laundry: hand in and handout of clothing rooms (G-0.8).

200

22

Photos: hand in and handout of orders (G-0.8).

200

23

Saunas - waiting and cooling. (G-0.8).

150

24

Rental points: Storages. (G-0.8).

150

25

Photos: The survey room of photo saloon. (G-0.8).

100

26

Saunas - pools. (on the floor, G-0.0).

100

27

Saunas - undressing, washing, shower and steaming rooms (on the floor, G-0,0).

75

28

Apparel Chemical Cleaning Shop: storage facilities for chemicals. (G-0.8).

50

Standards for the lighting of logistics centers



Lighted objects

Medium illumination
(Em), lx
at least

1

For closed warehouses for floor storage with gas-discharge lamps

75

2

For closed warehouses with incandescent lamps

50

3

For shelf storage with gas-discharge lamps

200

4

For shelf storage with incandescent lamps

100

5

For open warehouses

20

6

Reception and issuance expedition

150

7

Sorting and picking of goods

200

Hotel Lighting Standards



Lighted objects

Medium illumination
(Em), lx
at least

1

Service desk, duty and service staff. (G-0.8).

200

2

Guest rooms, rooms. (On the floor, G-0.0).

150

Lighting standards for residential buildings



Lighted objects

Medium illumination
(Em), lx
at least

1

Children rooms. (on the floor, G-0.0).

200

2

Living rooms, kitchens. (On the floor, G-0.0)

150

3

Buildings: Concierge facilities. (On the floor, G-0.0).

150

4

Hallways, baths, bathrooms. (On the floor, G-0.0).

50

5

Buildings: Lobbies. (On the floor, G-0.0).

30

6

Buildings: Floor and elevator halls, ladders, and stairwells. (On the floor, G-0.0).

20

Lighting standards for auxiliary buildings and facilities



Lighted objects

Medium illumination
(Em), lx
at least

1

Medical points: Procedural cabinets. (G-0.8).

500

2

Medical points: Doctors ' offices, first-aid rooms. (G-0.8).

300

3

Medical points: Waiting rooms, registry, duty staff rooms. (G-0.8).

200

4

Sanitary Facilities: Lavatories, latrines, smoking rooms. (On the floor, G-0.0).

75

5

Sanitary Facilities: Shower, wardrobe, laundry and footwear, and heat-dryer facilities. (On the floor, G-0.0).

50

Pharmacy Lighting Standards



Lighted objects

Medium illumination
(Em), lx
at least

1

Assistant, aseptic, analytic, filling, concentrates preparatory room and semi-finished goods, and control and marking. (G-0.8).

500

2

Prescription department, manual sales, optics, ready-made medications. (G-0.8).

300

3

Storage facilities for medicines and dressings, dishes. (G-0.8).

150

4

Storage of acids, disinfectioned means, fuel and flammable liquids. (G-0.8).

75

5

Container closet. (G-0.8).

50

Station Lighting Standards



Lighted objects

Medium illumination
(Em), lx
at least

1

Computing Center. (G-0.8).

400

2

Prescription department, manual sales, optics, ready-made medications. (G-0.8).

300

3

Waiting rooms, operations, cash halls, ticket baggage, liaison, operator, Dispatch. (G-0.8).

300

4

Rooms of the mother and child, long stay of the passengers room. (On the floor, G-0.0).

200

5

Distribution halls, hallways. (On the floor, G-0.0).

150

Lighting standards for parks, stadiums and exhibitions



Lighted objects

Medium illumination
(Em), lx
at least

1

Recreational areas, playgrounds in front of theatres, cinemas, exhibition pavilions and open entertainments; Tabletop Games: Exhibitions. (G-0.0).

20

2

Recreational areas, playgrounds in front of theatres, cinemas, exhibition pavilions and open entertainments; Tabletop Games: City parks and gardens of administrative districts. (G-0.0).

10

3

Main entrances: Stadiums and exhibitions. (G-0.0).

10

4

Central Alleys: Exhibitions. (G-0.0).

10

5

Recreation areas in exhibitions. (G-0.0).

10

6

Main entrances: City parks. (G-0.0).

6

7

Auxiliary entrances: Stadiums and exhibitions. (G-0.0).

6

8

Central Alleys: Stadiums. (G-0.0).

6

9

Side Alleys: Exhibitions. (G-0.0).

6

10

Main entrances: Gardens of administrative districts. (G-0.0).

4

11

Central Alleys: City parks. (G-0.0).

4

12

Side Alleys: Stadiums. (G-0.0).

4

13

Auxiliary entrances: City parks. (G-0.0).

2

14

Central Alleys: Gardens of administrative districts. (G-0.0).

2

15

Side Alleys: City parks. (G-0.0).

2

16

Auxiliary entrances: Gardens of administrative districts. (G-0.0).

1

17

Side Alleys: Gardens of administrative districts. (G-0.0).

1

Sports Facilities Lighting Standards

Sport


Class of the game or sport

Minimum horizontal illumination (Emin), lx

Open structures

Covered structures

1

Football

Training

50

300

Competition

100

500

2

Ice hockey, figure skating

Training

100

500

Competition

400

500

3

Hockey with a ball on the grass

Training

50

150

Competition

100

500

4

Ice skating

Training

50

150

Competition

100

500

5

Badminton, basketball, volleyball, hand-ball

Training

50

300

Competition

400

500

6

Tennis

Training

100

300

Competition

400

500

7

Table Tennis

Training

150

400

Competition

-

500

8

Akrobatics, gymnastics, fencing

Training

30

200

Competition

400

500

9

Boxing, wrestling

Training

30

200

Competition

-

1000

10

Athletics

Training

50

150

Competition

100

-

11

Heavy Athletics

Training

30

150

Competition

-

500

12

Swimming

Training

100

150

Competition

-

400

13

Water polo

Training

100

200

Competition

-

400

14

Diving


100

150

15

Jumping on a trampoline


-

200

16

Shooting


-

75

17

Chess Checkers


-

150

18

Gyms. (on the floor, G-0.0).


-

200

19

Covered pools. (On the surface of the water).


-

150

20

Aerobic halls, gymnastics, wrestling


-

200

Lighting standards for industrial facilities as per VSN 196-83
Industry standards for the design of artificial lighting of the main manufacturing plants of ministry
It was first implemented on January 1, 1984.



Lighted objects

Medium illumination
(Em), lx
at least

1. Foundries for the production and repair of machinery, machinery, structural rooms and metal

1.1

Provo Branch (fragmentation of scrap metal). Scrap yard, site, lifter landing. Walk through the workshop and workplace approaches. (G-0.0).

75

1.2

For mix preparation compartment of transporters. (G-0.8).

30

1.3

Mix Preparation Runners Branch. (G-0.8).

200

1.4

For mix Preparation Waltz Branch, filters. Bar department. Forming department overall level of illumination by branch. Fabrication of forms, assembly of bottles, placement of bars for large and medium molding. Technological processing of models, drying. office of knockout the overall level of illumination by branch. Mechanical cut forms and bars from bottles. (G-0.8).

150

1.5

Forming department Fabrication Molding forms. (G-0.8).

300

1.6

Bar section drying and storage of bars. Forming Department of bottles Supply and forms to fill. (G-0.0).

50

1.7

Filling section site of the inspection and repair of furnaces, furnaces. (G-0.0).

30

1.8

The site of bottle cooling. (G-0.0).

10

2. Forging rooms of the production and repair of machinery, machinery, steel and metal

2.1

Preparing department. Forging department. Mechanical division overall level of illumination by branch. (G-0.8).

200

2.2

Mechanical Branch tumbling drums. (G-0.8).

150

3. Cold stamping rooms, departments of production and repair of machinery, machinery, steel and metal

3.1

Overall level of illumination by workshop, department. Press, stamps, bending machines with manual feed. (G-0.8).

200

3.2

vending machines. (G-0.8).

150

4. Thermal rooms, departments of production and repair of machinery, machinery, steel and metal

4.1

Overall level of illumination by workshop, department. (G-0.8).

150

4.2

Thermal ovens, furnaces, HDTV, hardening baths, cooling baths. (G-0.8).

200

5. Rooms suppression, (galvanic rooms) production and repair of machinery, mechanisms, steel and metal

5.1

The overall level of illumination on the workshop. The tubs, the washing, the metal plating. (G-0.8).

200

5.2

QCD. (G-0.8).

500

5.3

Sewage treatment plants. (G-0.0).

10

6. Rooms of the production and repair of machinery, machinery, steel and metal

6.1

Procurement offices, parcels. (G-0.8).

200

6.2

Procurement offices, parcels in open sites. (G-0.8).

50

6.3

Drilling site. (G-0.8).

150

7. Welding and assembly-welding rooms, compartments, production and repair areas of machinery, machinery, assembly and Metal

7.1

The overall level of illumination on the workshop. Welding, cutting, melting. (G-0.8).

200

7.2

Markup, dabbing. (G-0.8).

300

8. Painting rooms production and repair of machinery, machinery, steel and metal

8.1

Painting Rooms The overall level of illumination on the workshop. Preparatory operations (clean-up, degreasing, primer painting). Painting of structures, construction machines, equipment, etc. (G 0.8).

200

9. Mechanical and instrumental ROOMSS, rooms snap-ins for the production and repair of machinery, machinery, steel and metal

9.1

Tubing-Mechanical room The overall level of illumination on the workshop. Processing of tubing complex design on radial-drilling machines. (G-0.8).

200

9.2

Mechanical, instrumental rooms, compartments, parcels, rooms snap-in the general level of illumination on the workshop (G-0.8).

300

9.3

Mechanical, tool rooms, compartments, parcels, roomsed snap-ins, plumbing, circle work, drawing work. (G-0.8).

500

9.4

Mechanical, instrumental rooms, branches, parcels, rooms of the QCD snap-ins. (G-0.8).

750

10. Repair and mechanical rooms production and repair of machinery, machinery, steel and metal

10.1

The overall level of illumination on the workshop. Dismantling machines, mechanisms. Dismantling of machine nodes, mechanisms after washing. (G-0.8).

200

10.2

Separation of engines, motors, pumps and other electric, hydraulic, pneumatic equipment. (G-0.8).

300

10.3

Division of repair of track-type vehicles. (G-0.8).

150

11. Welding rooms of the production and repair of machinery, machinery, steel and metal

11.1

Separates the assembly of large nodes of machines, machinery, and equipment. (G-0.8).

150

11.2

Separation of assembly of medium nodes of machinery, machinery, tools of small mechanization, equipment. A shop, a branch, a piece of assembly machines, machinery, and equipment. (G-0.8).

200

11.3

Separation of electrical, hydraulic, pneumatic equipment assembly. (G-0.8).

300

12. Electrical rooms production and repair of machinery, machinery, steel and Metal

12.1

The overall level of illumination on the workshop. Section of panels, remotes, cabinets, etc. (G 0.8).

200

12.2

A section of a wire, winding operations, assembly of fixtures, and other electrical equipment. (G-0.8).

300

13. Abrasive rooms of production and repair of machinery, machinery, steel and metal

13.1

The overall level of illumination on the workshop. Department of forming mass preparation. The branch, the section of the abrasive heat. (G-0.8).

150

13.2

Press department. (G-0.8).

200

13.3

Separation of mechanical treatment of the abrasions, hardness test and rupture, QCD. (G-0.8).

500

14. Concrete mixing Workshop for the production of RC and blocks structures and articles

14.1

Concerete mixing node overall luminance level by branch office. Concrete office. Mixer. (G-0.8).

10

14.2

Concrete office node dosing office. (G-0.8).

150

15. Reinforcing workshop for the production of RC and blocks structures and products

15.1

Reinforcing blank compartment The overall level of illumination by department. Welding shop, general level of illumination by workshop, department. Welding positions, vending machines, cars. Department of rebar assembly general level of illumination by compartment. (G-0.8).

200

16. Forming Workshop for the production of RC and blocks structures and articles

16.1

Forming workshop The overall level of illumination on the workshop. (G-0.8).

150

16.2

Humidity room. (G-0.8).

50

16.3

Section of the deck, insulation, finishing, QCD and marking. (G-0.8).

200

17. Production of silicate bricks

17.1

Grinding Department. The limestone roasting department. Grind branch. Mass preparing department (G-0.8).

75

17.2

Control of finished products. The press, the handlers. Forming Department. Overall level of illumination by department. (G-0.8).

200

18. Production of red clay brick

18.1

Roasting shop. (G-0.0).

75

18.2

Drying stoves. (G-0.8).

75

18.3

Control of finished products. (G-0.8).

200

19. Lime Production

19.1

Overall level of illumination by laboratory. Lab equipment, appliances. (G-0.8).

300

19.2

Overall level of illumination by department. (G-0.0).

75

20. Granite and Marble Treatment

20.1

Granite and marble rooms. The overall level of illumination by the workshops. (G-0.8).

150

20.2

Sawing up of the natural stone to the slabs. The cutting and reinforcement of slabs on the milling machines. (G-0.8).

200

20.3

Polishing of slabs. (G-0.8).

300

20.4

QCD. (G-0.8).

500

20.5

Packaging of finished slabs. (G-0.0).

75

21. Woodworking plants and rooms. Sawmill production.

21.1

Sites for the unloading (loading) of raw materials, sawnwood, finished goods from transport (to transport). (G-0.0).

10

21.2

Overall level of illumination by department. Sawmill frame (on the side of the log feed), second floor. Sawing up of wood on tape, circular, and pendulum saws. (G-0.8).

200

21.3

Department of sorting, rejection lumber. Lumber Processing Department. (G-0.8).

100

21.4

Waste processing and Transportation division, first floor. (G-0.8).

100

22. Woodworking plants and rooms. Carpentry.

22.1

Overall level of illumination by department. Site of cutting and marking. Automatic line. Assembly department. Department of clay preparation. Painting and varnish separation. (G-0.8).

150

22.2

Grinding machines. Window and door block glazing segments. Preparation and coverage of products with varnishes and paints. (G-0.8).

200

22.3

Texture pick areas and key labels. Polishing (cleaning) the surface of the product. (G-0.8).

300

23. Manufacturing of container and collection-type inventory

23.1

The overall level of illumination on the workshop. Site of assembly of volumetric blocks. Line of panels (vajmy, press, manipulators, beds, nail machines, stowage heater). (G-0.8).

150

23.2

Site of roof elements. Site of chamfering and splicing the boards along the length and section. Site of slab cutting by format. Site of gluing slabs. (G-0.8).

150

24. Production of wooden glued structures (DKK)

24.1

Overall level of illumination by department. (G-0.8).

150

24.2

Storage locations of the packages. (G-0.0).

50

25. Maintenance rooms, offices, sites

25.1

Overall level of illumination by workshop, department, site. (G-0.8).

300

25.2

Carbide, cutter, rolling. Sawing stamps for tooth punch. Assembly tables, inspection and control of ready-made tools, workbenches. (G-0.8).

300

25.3

Warehouses of metal, scrap metal, lumber, raw materials, crumbling material (gravel, sand, cement, etc.), finished products. (G-0.0).

20

26. Automobile Service Enterprises

26.1

Car washing and cleaning. (G-0.0).

150

26.2

Maintenance and repair of vehicles. (G-0.0).

200

26.3

Daily maintenance of vehicles. (V - on the machine).

75

26.4

Inspection ditches. (G - Bottom of the car).

150

26.5

Departments: Motor, aggregate, mechanical, electrical and power supply. (G-0.8).

300

26.6

Forging, welding and copper departments Carpentry and strips branches. Repair and installation of tyres. (G-0.8).

200

26.7

Car storage facilities. (G-0.0).

20

26.8

Open car storage sites. (G-0.0).

5

27. Boiler rooms

27.1

Boiler service sites. (G-0.0).

100

27.2

sites and ladders of boilers and economizerss, aisles behind the boilers. (G-0.0).

10

27.3

Pumps rooms, fans, bunker, fuel. (G-0.8).

100

27.4

Condensation, chemical water purification, aerator, boiler rooms (G-0.0).

100

27.5

Bin room. (Г-0.8).

20

28. Premises

28.1

Transformers and reactors ' rooms. (V-1.5).

50

28.2

Distribution unit rooms (V-1.5).

100

28.3

Battery room. (G-0.5).

50

28.4

Battery repair. (G-0.8).

200

29. Facilities for electric and electric forklifts

29.1

Parking and charging facilities. (G-0.0).

50

29.2

Repair of electric cars and electric forklifts. (G-0.0).

200

29.3

Electrolyte and distillation rooms. (G-0.8).

160

30. Engineering network facilities and other technical facilities

30.1

Ventilation facilities (except air conditioning). (G-0.8).

20

30.2

Air conditioning, pumps, heaters rooms. (G-0.8).

75

30.3

The machine rooms of the pumps, the compressors, the air blowers and the staff are constantly on duty. (G-0.8).

150

30.3

Machine rooms of the pumps, the compressors, air blowers without a permanent staff shift. (G-0.8).

100

30.4

Rooms for utility networks. (G-0.0).

20